Winterizing In-Floor Cleaning Systems
Protect pop-up heads, water distribution valves, and booster pumps from freeze damage with proper blow-out and antifreeze procedures.
Winterizing In-Floor Cleaning Systems
Protect pop-up heads, valves, and booster pumps from freeze damage
Maximum Air Pressure: 20 PSI
Higher pressure damages pop-up head mechanisms. Use 15-20 PSI maximum when blowing out lines.
Estimated Time: 1.5-3 Hours
Time varies by system complexity. 2-zone systems: ~90 minutes. 4+ zone systems: 2-3 hours. First-time winterization takes longer.
- • NEVER exceed 20 PSI air pressure when blowing out lines
- • ALWAYS turn off booster pump at breaker before opening canister
- • NEVER use automotive antifreeze - only propylene glycol
- • NEVER force WDV valve to closed position (damages internal gears)
- • NEVER force pop-up heads down if they're raised after blow-out
- • Replace cracked canister O-rings immediately (prevents air leaks)
T3 and Alpha III systems use spring-loaded WDV valves. Leave valve in mid-position (between zones). Don't force to full stop. Precision Nozzles require lower pressure (15 PSI max) due to smaller orifices.
Rotary valve module must be manually rotated to center position. Remove module and lubricate O-rings with silicone-based lubricant. Clean module ports thoroughly. PCC2000 requires antifreeze in each of 10 valve ports.
Older systems with gear-driven WDV. Remove and clean gears annually. Apply white lithium grease to gears before reassembly. Canister drain plug is 1/4" NPT - don't lose it. Heads are notorious for sticking - clean all heads before winter.
Venturi-powered systems have no moving valve. Blow out each zone line directly at manifold. Check Venturi nozzle for debris. No antifreeze needed in valve mechanism (no valve), but add to zone lines.
Identify Your In-Floor System Type
Different manufacturers have different winterization requirements.
Test System Before Winterization
Verify all zones are functioning properly before shutting down.
Blow Out In-Floor Lines
Remove water from underground plumbing to prevent freeze damage.
Add Antifreeze to In-Floor System
Protect remaining water in lines and valve mechanisms from freezing.
Protect Water Distribution Valve (WDV)
The heart of the system requires special winterization care.
Winterize Dedicated Booster Pump
Most in-floor systems use a dedicated 3/4-1 HP booster pump.
Address Pop-Up Head Concerns
Prevent head damage and make spring startup easier.
Final Inspection and Documentation
Complete winterization with proper storage and record-keeping.
Common Questions
Why are some pop-up heads stuck raised after blowing out?
This is completely normal. Air pressure lifts the heads, and without water flow, they may not fully retract. Do NOT force them down - the internal spring mechanism will reset when you refill and restart the system in spring. Forcing can damage the spring or seal.
Do I need to remove all pop-up heads for winter?
No. Most manufacturers recommend leaving heads installed. Removing heads risks losing springs, damaging seals, or debris entering head ports. Only remove heads if they're damaged and need replacement, or if manufacturer specifically requires it (rare).
How much antifreeze do I really need?
1-3 quarts for most systems. After blowing out, minimal water remains in lines. Antifreeze protects WDV valve mechanism and any trapped water near heads. Formula: 1 quart per 3 zones, plus 1 quart for canister/valve. If unsure, err on the side of more - excess won't hurt.
Can I use the main circulation pump instead of booster pump?
No. In-floor systems require dedicated booster pump for proper pressure and flow. Main pump pressure is too low to operate pop-up heads effectively. If your booster pump is broken, winterize the in-floor system as non-functional and use alternative cleaning method in spring until repaired.
What if I can't find my WDV canister?
Check equipment pad, under deck near booster pump, or in pool house. Some systems have in-deck canisters with flush-mount lids (look for 10-12 inch circular covers). Consult original pool builder plans or contact manufacturer with pool address for installation records. WDV must be winterized - don't skip this step.
Should I run the system before spring opening?
Yes, but only after fully refilling pool and priming booster pump. Run for 1-2 cycles to purge antifreeze and verify all heads are functioning. Expect pink water from antifreeze for first 30-60 minutes. Check for leaks at WDV canister and pump connections. Clean any heads that remain stuck.
Tools & Materials Required
Equipment:
- • Air compressor (15-20 PSI regulated) OR
- • Shop vac with blow function (6+ gallon capacity)
- • Rubber adapter/reducer for canister opening
- • Screwdriver (for canister lid and pump plugs)
- • Adjustable wrench or pliers
- • Bucket (for draining water from components)
- • Headlamp or flashlight (for inspections)
Materials:
- • 1-3 quarts propylene glycol pool antifreeze
- • Silicone-based lubricant for O-rings
- • Replacement O-ring for canister (if worn)
- • CLR or vinegar (for cleaning clogged heads)
- • Waterproof labels (for breaker panel)
- • Ziplock bags (for storing drain plugs)
- • Teflon tape (if removing threaded components)
Checklist
- 1Identify system type (A&A, Paramount PV3, Caretaker, Blue Square) and consult manual.
- 2Test system operation - verify all zones cycle and heads pop up correctly.
- 3Blow out in-floor lines with 15-20 PSI air pressure maximum (higher damages heads).
- 4Add 1-2 quarts antifreeze to canister and distribution valve.
- 5Protect water distribution valve - leave in mid-position, lubricate O-rings.
- 6Winterize dedicated booster pump - drain completely, add antifreeze to seal.
- 7Address pop-up heads - do NOT force down if raised after blow-out (damages springs).
- 8Document setup and store parts indoors - create spring startup checklist.
Related Playbooks
Comprehensive winterization for gas, electric, heat pump, solar, and hybrid heaters - prevent $1,500-$4,000 freeze damage.
Protect your pool through the off-season with nutrient control, equipment prep, and freeze safeguards.
Climate-specific winterization strategies by USDA zone - drain depth conventions, skimmer protection methods, and regional best practices.